Abstract
In order to rationalize the lightning protection design of distribution lines, lightning phenomena on TEPCO's distribution lines were continuously observed. The observations were carried out with still cameras and lightning surge monitoring sensors. The results elucidate the lightning performance of distribution lines. For example, direct lightning strokes are the major cause of the present distribution line faults. This fact suggests that it is important to investigate observation data on direct lightning strokes. The observation data were analyzed by means of a direct lightning analysis model. The calculated waveforms were compared with the measured waveforms on distribution lines. The probability distributions of the surge currents and voltages were calculated by the Monte Carlo method. These results provide new data on lightning performance.
Original language | English |
---|---|
Pages (from-to) | 28-37 |
Number of pages | 10 |
Journal | Electronics and Communications in Japan, Part II: Electronics (English translation of Denshi Tsushin Gakkai Ronbunshi) |
Volume | 91 |
Issue number | 10 |
DOIs | |
Publication status | Published - 2008 Dec 1 |
Externally published | Yes |
Keywords
- Cumulative frequency
- Direct stroke
- Distribution line
- Indirect stroke
- Lightning
- Surge