A study on design review of the control performance of the air conditioning to prevent room pressure change troubles

Daiki Tanaka*, Takamitsu Koike, Nobuhiro Tanaka, Takayuki Miyake, Shigeyuki Tateno, Hisayoshi Matsuyama

*Corresponding author for this work

Research output: Chapter in Book/Report/Conference proceedingConference contribution

Abstract

It is very important to keep different pressure among rooms with different cleanness in pharmaceutical factories, semiconductor factories and so on. However, a trouble, that caused by the room pressure changes, is frequently detected at commissioning systems and results in significant losses of time and money. A method of design review, by use of a simulation, is proposed in this paper to prevent trouble of room pressure change. The commissioning test removes the causes of the trouble in the design stage. This paper notes simulation results of the air-conditioning systems. The simulator is made by MATLAB and SMULINK. The developed method of this simulator is expounded by use of Base-model in which all kind of elements of air-conditioning components are included. When room pressure of the Base-model is controlled, the simulator measures room pressure change and flow rate change. The simulator can evaluate the systems beforehand only by design information. As an example of evaluation of the systems, an actual air-conditioning system, where the room pressure change trouble occurs, is verified. It adequately explains the cause and solution of this trouble.

Original languageEnglish
Title of host publication2006 SICE-ICASE International Joint Conference
Pages5573-5578
Number of pages6
DOIs
Publication statusPublished - 2006 Dec 1
Event2006 SICE-ICASE International Joint Conference - Busan, Korea, Republic of
Duration: 2006 Oct 182006 Oct 21

Publication series

Name2006 SICE-ICASE International Joint Conference

Conference

Conference2006 SICE-ICASE International Joint Conference
Country/TerritoryKorea, Republic of
CityBusan
Period06/10/1806/10/21

Keywords

  • Air conditioning
  • MATLAB
  • Room pressure trouble
  • SIMULINK
  • Simulation

ASJC Scopus subject areas

  • Computer Science Applications
  • Control and Systems Engineering
  • Electrical and Electronic Engineering

Fingerprint