Abstract
A special active filter, which can eliminate the variable harmonic currents in continuity, was investigated. A variable-frequency band-pass filter was developed for the extraction of current component of fundamental frequency. Dynamic simulations for the active filter, motor generator with a flywheel (FW-MG) and power supplies of heating devices for the experimental fusion device of LHD have been carried. We found that the harmonic currents with the amplitudes of 20% have been reduced to less than 2% in the operational frequency range from 95 Hz to 55 Hz by using this active filter.
Original language | English |
---|---|
Pages (from-to) | 93-97 |
Number of pages | 5 |
Journal | Fusion Engineering and Design |
Volume | 75-79 |
Issue number | SUPPL. |
DOIs | |
Publication status | Published - 2005 Nov |
Externally published | Yes |
Keywords
- Active filter
- Harmonic current
- LHD
- Motor generator
ASJC Scopus subject areas
- Civil and Structural Engineering
- Nuclear Energy and Engineering
- Materials Science(all)
- Mechanical Engineering