Abstract
We have developed a novel evaluation technique of the deterioration degree of insulators for breakers using a chemical analysis and the Mahalanobis-Taguchi (MT) method. It is possible to evaluate the deterioration degree with great accuracy and nondestructively on-site by this technique without the effect of humidity and external noise such as electromagnetic wave. The mechanism of insulator's surface resistivity reduction was clarified, and it was found that the deterioration degree of insulators could be evaluated by this technique because a linear relationship existed between the results judged by the MT method and the actual measurement results for surface resistivity. In comparison to electrical methods such as partial electric discharge and megohmmeters, the evaluation accuracy has been improved by three digits and the range of the deterioration degree that could be evaluated was expanded by seven digits.
Original language | English |
---|---|
Pages (from-to) | 1033-1040+8 |
Journal | IEEJ Transactions on Power and Energy |
Volume | 127 |
Issue number | 9 |
DOIs | |
Publication status | Published - 2007 |
Externally published | Yes |
Keywords
- Breakers
- Chemical analysis
- Evaluation of deterioration degree
- Insulators
- Mahalanobis-Taguchi method
ASJC Scopus subject areas
- Energy Engineering and Power Technology
- Electrical and Electronic Engineering