TY - JOUR
T1 - Experimental and numerical performance evaluation of double-lift absorption heat transformer
AU - Saito, Kiyoshi
AU - Inoue, Naoyuki
AU - Nakagawa, Yasuaki
AU - Fukusumi, Yukihiro
AU - Yamada, Hiroyuki
AU - Irie, Tomoyoshi
N1 - Funding Information:
This work is supported by New Energy and Industrial Technology Development Organization (NEDO).
Publisher Copyright:
© 2015 ASHRAE.
PY - 2015
Y1 - 2015
N2 - In this study, a two-stage absorption heat transformer was investigated, which can generate high-temperature steam of approximately 180◦C driven by waste heat from hot water below 90◦C. A model-scale (steam 14 kW) apparatus and a practical-scale (steam 200 kW) test apparatus were designed and built. Test operations of the apparatus were conducted, and the function and effectiveness of the heat transformers were verified.
AB - In this study, a two-stage absorption heat transformer was investigated, which can generate high-temperature steam of approximately 180◦C driven by waste heat from hot water below 90◦C. A model-scale (steam 14 kW) apparatus and a practical-scale (steam 200 kW) test apparatus were designed and built. Test operations of the apparatus were conducted, and the function and effectiveness of the heat transformers were verified.
UR - http://www.scopus.com/inward/record.url?scp=84940371672&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=84940371672&partnerID=8YFLogxK
U2 - 10.1080/23744731.2014.998937
DO - 10.1080/23744731.2014.998937
M3 - Article
AN - SCOPUS:84940371672
SN - 2374-4731
VL - 21
SP - 312
EP - 322
JO - Science and Technology for the Built Environment
JF - Science and Technology for the Built Environment
IS - 3
ER -