TY - JOUR
T1 - Temperature and Pressure Distribution Simulations of 3-km-Long High-Temperature Superconducting Power Cable System with Fault Current for 66-kV-Class Transmission Lines
AU - Yasui, Tetsuo
AU - Takeda, Natsuko
AU - Yokoo, Yusuke
AU - Agatsuma, Ko
AU - Ishiyama, Atsushi
AU - Wang, Xudong
AU - Masuda, Takato
AU - Morimura, Toshiya
AU - Mimura, Tomoo
N1 - Publisher Copyright:
© 2017 IEEE.
PY - 2017/6
Y1 - 2017/6
N2 - A computer program has been developed by numerically solving the nonlinear heat conduction and heat transfer equations, which are discretized using the finite difference method, to calculate the temperature and pressure distributions in high-temperature superconducting (HTS) power cables cooled using liquid nitrogen (LN2). The LN2 coolant properties are estimated using Cryodata's GASPAK software package. This evaluation of the temperature and pressure distributions is important to understand how we can make practical use of HTS power cables and to assess the effects of short-circuit accidents. To incorporate HTS power cables into real grids, it is necessary to evaluate HTS power cables that are a few kilometers long. In this study, 3-km-long HTS cables were evaluated using our proposed computer program. This program was used to model the cooling system, ac loss, dielectric loss, and intermediate-joint losses. The results revealed that the temperature of the LN2 coolant at the cable outlet could reach the saturation temperature when a fault current of 31.5 kA flowed for 2 s (worst case for the 66-kV-class transmission lines in Japan). From the results, it was also clear that the effects of the ac loss, dielectric loss, and intermediate-joint losses on the increase in the temperature of the LN2 coolant could not be ignored.
AB - A computer program has been developed by numerically solving the nonlinear heat conduction and heat transfer equations, which are discretized using the finite difference method, to calculate the temperature and pressure distributions in high-temperature superconducting (HTS) power cables cooled using liquid nitrogen (LN2). The LN2 coolant properties are estimated using Cryodata's GASPAK software package. This evaluation of the temperature and pressure distributions is important to understand how we can make practical use of HTS power cables and to assess the effects of short-circuit accidents. To incorporate HTS power cables into real grids, it is necessary to evaluate HTS power cables that are a few kilometers long. In this study, 3-km-long HTS cables were evaluated using our proposed computer program. This program was used to model the cooling system, ac loss, dielectric loss, and intermediate-joint losses. The results revealed that the temperature of the LN2 coolant at the cable outlet could reach the saturation temperature when a fault current of 31.5 kA flowed for 2 s (worst case for the 66-kV-class transmission lines in Japan). From the results, it was also clear that the effects of the ac loss, dielectric loss, and intermediate-joint losses on the increase in the temperature of the LN2 coolant could not be ignored.
KW - Cooling system
KW - LN coolant
KW - fault current
KW - high-temperature superconducting power cable
KW - saturation temperature
UR - http://www.scopus.com/inward/record.url?scp=85014966761&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=85014966761&partnerID=8YFLogxK
U2 - 10.1109/TASC.2017.2656631
DO - 10.1109/TASC.2017.2656631