Abstract
This study focuses on the thermal comfort provided by radiant cooling and heating systems in Asia. For this purpose, a field survey was conducted during the summer in a Japanese office with radiant ceiling panel cooling systems. Indoor environment measurements were made and questionnaires were handed out to the workers. By using these measurements and questionnaires, the thermal comfort provided by radiant ceiling panel cooling systems in Asia was evaluated. Three results were obtained from the indoor environment measurements. First, because the air temperature was higher in the upper floors, the necessity for thermal insulation was recognized. Second, because the radiant temperature (in the range of 1.5-3.0 °C) was lower than the air temperature, a radiant cooling effect was realized. Finally, almost all of the workers were satisfied with the minimal air flow rate.
Original language | English |
---|---|
Pages | 169-174 |
Number of pages | 6 |
Publication status | Published - 2014 |
Event | 13th International Conference on Indoor Air Quality and Climate, Indoor Air 2014 - Hong Kong, Hong Kong Duration: 2014 Jul 7 → 2014 Jul 12 |
Conference
Conference | 13th International Conference on Indoor Air Quality and Climate, Indoor Air 2014 |
---|---|
Country/Territory | Hong Kong |
City | Hong Kong |
Period | 14/7/7 → 14/7/12 |
Keywords
- Field survey
- Radiant ceiling panel cooling system
- Thermal comfort
ASJC Scopus subject areas
- Pollution
- Building and Construction
- Health, Toxicology and Mutagenesis
- Computer Science Applications