Abstract
A fault locator system in a loop-shaped distribution system with inverter based distributed generations is proposed. The fault locator system is based on measured impedances calculated by voltage and current at a transformer feeder of the distribution substation and incoming feeder of the inverter based distributed generations. The validity of the fault locator system was investigated by PSCAD/EMTDC simulations. It is assumed that a three-phase short-circuit fault occurs in the loop-shaped distribution system and the proposed fault locator system estimates the fault location. The estimation error in regard to fault location was described on the basis of simulation results. A primary factor in the estimation error was identified as the rate of change of measured impedance with fault location. It was found that the effect of significant digits of the measured impedance on the estimation error in regard to the fault location.
Original language | English |
---|---|
Title of host publication | 17th Power Systems Computation Conference, PSCC 2011 |
Publisher | Power Systems Computation Conference ( PSCC ) |
ISBN (Print) | 9789175012575 |
Publication status | Published - 2011 |
Event | 17th Power Systems Computation Conference, PSCC 2011 - Stockholm, Sweden Duration: 2011 Aug 22 → 2011 Aug 26 |
Other
Other | 17th Power Systems Computation Conference, PSCC 2011 |
---|---|
Country/Territory | Sweden |
City | Stockholm |
Period | 11/8/22 → 11/8/26 |
Keywords
- Distribution system
- Inverter based distributed generation
- Measured impedance
- Protection system
ASJC Scopus subject areas
- Computer Networks and Communications
- Computer Science Applications
- Energy Engineering and Power Technology
- Electrical and Electronic Engineering