A field survey on indoor air pollution in school classrooms with different ventilation methods

Ko Murakami*, Kenta Sakai, Daisuke Nakamura, Haruno Ishikawa, Sayana Tsushima, Shin Ichi Tanabe

*この研究の対応する著者

研究成果: Conference article査読

4 被引用数 (Scopus)

抄録

The purpose of this study was to investigate the actual indoor air quality within two elementary schools with different types of ventilation methods, and to obtain data pertaining to the emission of bioeffluents within the schools. Field surveys on indoor air quality were conducted at two public elementary schools in Tokyo, both equipped with air-conditioning systems. School-A was also equipped with a heat-exchange ventilation system, while School-B did not have a ventilation system. Results of the study revealed that the target ventilation volume for the heat-exchange ventilation system in School-A was not achieved, indoor air quality in School-B was better in relatively cool conditions than School-A because of the habit of opening windows attached, there was a positive correlation between nonanal and decanal and CO2 concentration in summer, and the concentration of bioeffluents nonanal and decanal may be higher at high temperatures even under the same level of ventilation.

本文言語English
論文番号01020
ジャーナルE3S Web of Conferences
111
DOI
出版ステータスPublished - 2019 8月 13
イベント13th REHVA World Congress, CLIMA 2019 - Bucharest, Romania
継続期間: 2019 5月 262019 5月 29