抄録
In order to rationalize the lightning protection design of distribution lines, lightning phenomena on TEPCO's distribution lines were continuously observed. The observations were carried out with still cameras and lightning surge monitoring sensors. The results elucidate the lightning performance of distribution lines. For example, direct lightning strokes are the major cause of the present distribution line faults. This fact suggests that it is important to investigate observation data on direct lightning strokes. The observation data were analyzed by means of a direct lightning analysis model. The calculated waveforms were compared with the measured waveforms on distribution lines. The probability distributions of the surge currents and voltages were calculated by the Monte Carlo method. These results provide new data on lightning performance.
本文言語 | English |
---|---|
ページ(範囲) | 28-37 |
ページ数 | 10 |
ジャーナル | Electronics and Communications in Japan, Part II: Electronics (English translation of Denshi Tsushin Gakkai Ronbunshi) |
巻 | 91 |
号 | 10 |
DOI | |
出版ステータス | Published - 2008 12月 1 |
外部発表 | はい |
ASJC Scopus subject areas
- 物理学および天文学(全般)
- コンピュータ ネットワークおよび通信
- 電子工学および電気工学