An experimental validation of lightning performance in distribution lines

Teru Miyazaki*, Shigemitsu Okabe, Shigemitsu Sekioka

*この研究の対応する著者

研究成果: Article査読

18 被引用数 (Scopus)

抄録

The Tokyo Electric Power Company had conducted field research of voltages and currents in actual distribution lines due to lightning strokes between 1997 and 2001. These results confirm that the distribution line faults are mainly caused by direct lightning strokes to the line. Thus, it is important to simulate lightning performance for direct strokes to establish a lightning protection design of distribution lines. In this paper, statistical data of the observed voltages and currents are analyzed, and the validation of the observation results for the direct lightning strokes using a lightning surge analysis model is conducted. The observation results and the simulation model are useful in clarifying lightning performance in distribution lines.

本文言語English
ページ(範囲)2182-2190
ページ数9
ジャーナルIEEE Transactions on Power Delivery
23
4
DOI
出版ステータスPublished - 2008 8月 12
外部発表はい

ASJC Scopus subject areas

  • エネルギー工学および電力技術
  • 電子工学および電気工学