Consideration on transient stability assessment using deceleration area by the SIME

Megumi Suzuki*, Wataru Fujii, Shinichi Iwamoto

*この研究の対応する著者

    研究成果: Conference contribution

    4 被引用数 (Scopus)

    抄録

    At present, we often use critical clearing time and stability margin as the evaluation indices of the transient stability. We can calculate these indices by the SIME. But these calculations rely on simulation of unstable cases. However, in daily operations, power systems hardly fall into the unstable state and we operate in the stable case. We can operate the power systems more stably and effectively if we know stability margin in the stable power systems. In this paper, we propose a method using the deceleration area of the power-angle representation for transient stability assessment in the stable case. The SIME can assess transient stability of multi-machine power systems and detailed modeling fast. However, the SIME could not well handle simulations of stable cases, while the proposed method is able to expand the advantages of the SIME in simulations of stable cases. To investigate the validity of the proposed method, we show examples of 3-machine 9-bus systems.

    本文言語English
    ホスト出版物のタイトル2005 IEEE Power Engineering Society General Meeting
    ページ1695-1700
    ページ数6
    2
    出版ステータスPublished - 2005
    イベント2005 IEEE Power Engineering Society General Meeting - San Francisco, CA
    継続期間: 2005 6月 122005 6月 16

    Other

    Other2005 IEEE Power Engineering Society General Meeting
    CitySan Francisco, CA
    Period05/6/1205/6/16