Determination of optimal system configuration in Japanese secondary power systems

Yasuhiro Hayashi*, Junya Matsuki

*この研究の対応する著者

研究成果: Article査読

6 被引用数 (Scopus)

抄録

In Japan, when a secondary radial power system (66 kV, 77 kV) has a number of connected feeders whose circuit breakers (CBs) can be opened or closed, the combinatorial number of possible system structures created by switching CBs becomes very large. In order to determine the optimal configuration of secondary radial power system in normal state and fault state, a new computation algorithm is proposed. The proposed algorithm is based on enumeration and Reduced Ordered Binary Decision Diagram (ROBDD). In order to verify the availability of the proposed approach, the authors obtain optimal configurations for normal and fault states on IEE of Japan secondary power system model (IEEJ model) by using the proposed method. IEEJ model has the distinctive characteristics of practical Japanese power systems, the total number of configuration candidates is the 76th power of 2 (=75 000 000 000 000 billion approximately). The optimality of the system configuration obtained by the proposed method is mathematically guaranteed.

本文言語English
ページ(範囲)394-399
ページ数6
ジャーナルIEEE Transactions on Power Systems
18
1
DOI
出版ステータスPublished - 2003 2月
外部発表はい

ASJC Scopus subject areas

  • エネルギー工学および電力技術
  • 電子工学および電気工学

フィンガープリント

「Determination of optimal system configuration in Japanese secondary power systems」の研究トピックを掘り下げます。これらがまとまってユニークなフィンガープリントを構成します。