抄録

There is a danger of power generation efficiency decreasing due to voltage increase when clustered residential PV systems are grid-interconnected to a single distribution line. As a countermeasure, installation of the reactive power control of an inverter at each residence has been considered. In the previous research we demonstrated that about 20 percent of the output suppression loss was eliminated with reactive power control including PV voltage control when 225 residential PV were grid-interconnected. However, this was on a typical sunny spring day, the seasonal change of PV output and load power was not considered. So in this research we evaluated improved and smoothed generation efficiency among all residences with power factor and reactive power operating voltage through residential PV voltage control on clustered residential grid-interconnected PV for a period of one year.

本文言語English
ホスト出版物のタイトル2012 3rd IEEE PES Innovative Smart Grid Technologies Europe, ISGT Europe 2012
DOI
出版ステータスPublished - 2012 12月 1
イベント2012 3rd IEEE PES Innovative Smart Grid Technologies Europe, ISGT Europe 2012 - Berlin, Germany
継続期間: 2012 10月 142012 10月 17

出版物シリーズ

名前IEEE PES Innovative Smart Grid Technologies Conference Europe

Conference

Conference2012 3rd IEEE PES Innovative Smart Grid Technologies Europe, ISGT Europe 2012
国/地域Germany
CityBerlin
Period12/10/1412/10/17

ASJC Scopus subject areas

  • コンピュータ ネットワークおよび通信
  • 情報システム

フィンガープリント

「Evaluating improved generation efficiency: One year using residential PV voltage control with a clustered residential grid-interconnected PV」の研究トピックを掘り下げます。これらがまとまってユニークなフィンガープリントを構成します。

引用スタイル