TY - JOUR
T1 - Improvement of two-phase refrigerant distribution for upward flow of a parallel flow minichannel heat exchanger using insertion devices
AU - Kim, Nae Hyun
AU - Kim, Cheol Hwan
AU - Shah, Yousaf
AU - Li, Wei
N1 - Funding Information:
This work was supported by the Incheon National University Research Grant in 2017.
Publisher Copyright:
© 2019 Elsevier Ltd
PY - 2019/9
Y1 - 2019/9
N2 - In a parallel flow heat exchanger, significant mal-distribution of flow occurs due to phase separation. In this study, various insert devices (perforated tube, perforated tube with perforated plate, orifice and perforated tube, concentric perforated tube) were investigated to obtain an improved flow distribution in a 36 channel parallel flow heat exchanger. The test section was made to closely simulate an actual heat exchanger. Tests were conducted for upward flow for the mass flux from 57 to 241 kg m−2 s−1 and quality from 0.2 to 0.4 using R-410A. Of the investigated insert devices, concentric perforated tube yielded the best flow distribution. Insertion of the concentric perforated tube reduced the thermal degradation from 61% to 14%. Furthermore, the preferred number of holes of the concentric perforated tube was dependent on the mass flux. At a low mass flux, an insert having small number of holes was preferred, whereas the reverse was true at a high mass flux. At a low mass flux, the effect of inlet vapor quality on flow distribution was significant. At a high mass flux, however, the effect of vapor quality on flow distribution was minimal. Possible explanations on the flow distribution behavior were provided through flow visualization in the header.
AB - In a parallel flow heat exchanger, significant mal-distribution of flow occurs due to phase separation. In this study, various insert devices (perforated tube, perforated tube with perforated plate, orifice and perforated tube, concentric perforated tube) were investigated to obtain an improved flow distribution in a 36 channel parallel flow heat exchanger. The test section was made to closely simulate an actual heat exchanger. Tests were conducted for upward flow for the mass flux from 57 to 241 kg m−2 s−1 and quality from 0.2 to 0.4 using R-410A. Of the investigated insert devices, concentric perforated tube yielded the best flow distribution. Insertion of the concentric perforated tube reduced the thermal degradation from 61% to 14%. Furthermore, the preferred number of holes of the concentric perforated tube was dependent on the mass flux. At a low mass flux, an insert having small number of holes was preferred, whereas the reverse was true at a high mass flux. At a low mass flux, the effect of inlet vapor quality on flow distribution was significant. At a high mass flux, however, the effect of vapor quality on flow distribution was minimal. Possible explanations on the flow distribution behavior were provided through flow visualization in the header.
KW - Evaporator
KW - Flow distribution
KW - Header
KW - Insert device
KW - Parallel flow heat exchanger
KW - R-410A
UR - http://www.scopus.com/inward/record.url?scp=85068454432&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=85068454432&partnerID=8YFLogxK
U2 - 10.1016/j.applthermaleng.2019.114065
DO - 10.1016/j.applthermaleng.2019.114065
M3 - Article
AN - SCOPUS:85068454432
SN - 1359-4311
VL - 160
JO - Applied Thermal Engineering
JF - Applied Thermal Engineering
M1 - 114065
ER -