Performance analysis of desiccant dehumidification systems driven by low-grade heat source

Jongsoo Jeong*, Seiichi Yamaguchi, Kiyoshi Saito, Sunao Kawai

*この研究の対応する著者

研究成果: Article査読

61 被引用数 (Scopus)

抄録

If a desiccant dehumidification system can be driven by a heat source whose temperature is below 50 °C, exhaust heat from devices such as fuel cells or air conditioners can be used as its heat source, thereby saving energy. Therefore, in this study, we used a previously validated simulation model to determine the minimum heat source temperature for driving a desiccant dehumidification system. We considered four desiccant dehumidification systems that can be driven by waste heat - conventional desiccant-type systems (wheel type and batch type with only desiccant), a system with a precooler, double-stage-type systems (a type with two desiccant wheels and a four-partition desiccant wheel type), and a batch-type system with an internal heat exchanger. We found that among these systems, the last system can be driven by the lowest heated air temperature - approximately 33 °C - which is considerably lower than that of the conventional system.

本文言語English
ページ(範囲)928-945
ページ数18
ジャーナルInternational Journal of Refrigeration
34
4
DOI
出版ステータスPublished - 2011 6月

ASJC Scopus subject areas

  • 建築および建設
  • 機械工学

フィンガープリント

「Performance analysis of desiccant dehumidification systems driven by low-grade heat source」の研究トピックを掘り下げます。これらがまとまってユニークなフィンガープリントを構成します。

引用スタイル