T1 - Remaining service life diagnostic technology of insulators for power distribution equipment
AU - Miki, Shinsuke
AU - Okazawa, Hiroshi
AU - Hasegawa, Taketoshi
AU - Tsunoda, Sei
AU - Inujima, Hiroshi
N1 - Copyright:
Copyright 2020 Elsevier B.V., All rights reserved.
PY - 2007
Y1 - 2007
N2 - We have developed a remaining service life diagnostic technology for insulators, which are important parts involved in determining the service life of power distribution equipment. Application of chemical evaluation and the Mahalanobis-Taguchi method enabled us to diagnose the insulators' degree of deterioration with great accuracy and nondestructively on-site. The theory, which derives the threshold value of surface resistivity for electric discharge initiation calculated from rated voltage, the form of an insulator, etc., was established and a remaining service life was presumed from the diagnostic results by the MT method and the year in which the master curve of service life and the threshold value intersect. It was clarified that a remaining service life could be presumed by this technology because there was a good relationship between the check examination results of electric discharge initiation in the laboratory and the presumption results.
AB - We have developed a remaining service life diagnostic technology for insulators, which are important parts involved in determining the service life of power distribution equipment. Application of chemical evaluation and the Mahalanobis-Taguchi method enabled us to diagnose the insulators' degree of deterioration with great accuracy and nondestructively on-site. The theory, which derives the threshold value of surface resistivity for electric discharge initiation calculated from rated voltage, the form of an insulator, etc., was established and a remaining service life was presumed from the diagnostic results by the MT method and the year in which the master curve of service life and the threshold value intersect. It was clarified that a remaining service life could be presumed by this technology because there was a good relationship between the check examination results of electric discharge initiation in the laboratory and the presumption results.
KW - Chemical evaluation
KW - Electric discharge
KW - Insulators
KW - Mahalanobis-Taguchi method
KW - Power distribution equipment
KW - Remaining service life diagnosis
UR - http://www.scopus.com/inward/record.url?scp=34547236673&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=34547236673&partnerID=8YFLogxK
U2 - 10.1541/ieejpes.127.863
DO - 10.1541/ieejpes.127.863
M3 - Article
AN - SCOPUS:34547236673
SN - 0385-4213
VL - 127
SP - 863-869+13
JO - IEEJ Transactions on Power and Energy
JF - IEEJ Transactions on Power and Energy
IS - 7