抄録
Probability distribution of surge discharging current of arresters provided a basis for conventional theory of grounding systems. In order to rationalize the grounding systems, it is necessary to grasp the statistical data of lightning surges on distribution lines caused by direct lightning strokes and indirect lightning strokes. Lightning phenomena on TEPCO's distribution lines had been continuously observed for the rationalization of lightning protection design of distribution lines. The observation had been carried out with still cameras and monitoring sensors of lightning surges. This makes it possible to find out new interesting facts that can be useful for rationalization of lightning protection design of distribution lines. Cumulative frequency distribution of conventional data is close to that of ZnO discharging current in case of direct strokes and indirect strokes through TEPCO's observation. Moreover, to verify the cumulative current distribution in concrete poles, the authors have compared the cumulative distribution of current through ground lines with that of current through ground lines and concrete poles. The result shows that the distribution of current through ground lines and concrete poles is larger than that of current through only ground lines for high currents exceeding 1 kA. This fact suggests that lightning surge current flows not only in ground lines but also in concrete poles.
本文言語 | English |
---|---|
ページ(範囲) | 97-104+13 |
ジャーナル | IEEJ Transactions on Power and Energy |
巻 | 126 |
号 | 1 |
DOI | |
出版ステータス | Published - 2006 10月 16 |
外部発表 | はい |
ASJC Scopus subject areas
- エネルギー工学および電力技術
- 電子工学および電気工学