Thermal responsiveness of fusible sprinkler and its actuation below a confined ceiling

Yuji Hasemi, Shinji Sako

研究成果: Article査読

抄録

In order to improve the predictability of sprinkler response time for a confined ceiling, thermal properties of fusible sprinkler and environment of sprinklers below a confined ceiling during fire are discussed. A method of estimating the heat loss from a fusible link of the sprinkler fitting and the response of the link to external radiation is proposed. Measurements of temperature, velocity, radiation, and sprinkler response time below a ceiling are made in a 1 1.1m × 8.1m confined enclosure. The measured temperature and velocity are found to be close to previous theory for an unconfined ceiling if a correction for the existence of smoke layer is applied. Finally measured sprinkler response time is compared with calculation based on measured temperature, velocity and radiation history. The result shows the significance of radiation from the fire source in the determination of sprinkler response times.

本文言語English
ページ(範囲)1-10
ページ数10
ジャーナルBulletin of Japan Association for Fire Science and Engineering
38
1
出版ステータスPublished - 1988 1月 1
外部発表はい

ASJC Scopus subject areas

  • 材料科学(全般)
  • 安全性、リスク、信頼性、品質管理
  • 工学(全般)