Transient stability preventive control using CCT and generation margin

Hiroshi Takada*, Yoshinori Kato, Shinichi Iwamoto

*この研究の対応する著者

    研究成果: Conference contribution

    5 被引用数 (Scopus)

    抄録

    In recent years, power systems have become larger and more complicated. Deregulation of electric power industries has begun in some countries and power system operation is becoming more difficult. But the stability of the power supply is most important consideration for customers. Therefore power system operators consider not only economic load dispatch but also on-line stability aspect. In this paper, we pay attention to one of the most important transient stability indices. Critical Clearing Time (CCT), and propose a new transient stability preventive control method using generation rescheduling to satisfy predefined target CCTs. At first, contingency screening is carried out to select severe contingencies that have smaller CCTs than the target CCT. Rescheduled generator outputs are determined using the linear relationship between the generator output at the faulted bus and CCT and generation margins that indicate the surplus generation capabilities of generators. The proposed method is demonstrated using a 9 machine 20 bus system.

    本文言語English
    ホスト出版物のタイトルProceedings of the IEEE Power Engineering Society Transmission and Distribution Conference
    ページ881-886
    ページ数6
    2
    SUMMER
    出版ステータスPublished - 2001
    イベント2001 IEEE Power Engineering Society Summer Meeting - Vancouver, BC
    継続期間: 2001 7月 152001 7月 19

    Other

    Other2001 IEEE Power Engineering Society Summer Meeting
    CityVancouver, BC
    Period01/7/1501/7/19

    ASJC Scopus subject areas

    • エネルギー(全般)
    • 工学(全般)

    フィンガープリント

    「Transient stability preventive control using CCT and generation margin」の研究トピックを掘り下げます。これらがまとまってユニークなフィンガープリントを構成します。

    引用スタイル